Accessories for the installation of fire protection systems according to EN54.

PRODUCT CODE:
52002
EMPLOYMENT:
Fire alarm system
PACKAGE:
Beige ABS wall-mounted enclosure, electronic board
VARIANTS:

CHARACTERISTICS:

Beige ABS wall-mounted enclosure equipped with panel with LEDs for indications, push-buttons and key switch [52002].

SPECIFICATIONS:

Body dimensions240 x 150 x 48 mm
Power supply:- Main: from mains 250 Vac 50-60 Hz
- Auxiliary: supplied by No. 2 batteries 12 Vdc 1.1 / 1.3 Ah (Art. 00112 mandatory and supplied separately)
Operating area:Single
Main panel with LEDs for illuminated indications of the operating status of the control unit, with the following displays: - Fire alarm
- Mains voltage presence / absence
- Presence / absence of auxiliary voltage (battery)
- Central unit general fault
- Detector(s) line failure
- Line failure of remote alarm activation button(s)
- Manual out-of-service status of the control unit
- Siren line failure
- Feeding electromagnets
- System failure
Buttons:- Manual override of siren line and push-button and detector lines
- Recovery from alarm, fault or out-of-service condition
Key switch:For access to the central unit's Level 2 functions
Inputs (on terminal board):- Heat and smoke detector line(s) (up to 8 units, mandatory and supplied separately,
certified EN54-5 - heat Art. 05204A and EN54-7 - smoke Art. 05203A)
- Remote alarm activation button(s) line (up to 5 units, min. 2 mandatory supplied separately, EN54-11 certified Art. 05110R)
- Line remote button(s) manual release electromagnets
- External buzzer alarm silencing/reactivation button after alarm (Art. No. 05115)
Outputs (on terminal board):- Electromagnets line (up to 4 - 24 Vdc - Max. 300 mA total)
- Output for connection to up to 2 external sirens (additional mandatory electronic siren supplied separately and EN54-3 certified, Art. 05207)
operating in parallel with the internal ringer of the control unit
- N°1 relay output on COM. / N.O. / N.C. contacts (2 A) for signalling
external out-of-service / central unit failure
Other expected functions:- Mains presence / power failure signalling
- Auxiliary presence/voltage failure signalling (batteries)
- Checking the quality status of batteries
- Muting the alarm signal of the control unit
- Reactivation of alarm signalling following a new alert
alarm by any of the detection devices
- Possibility to put the control unit out of service manually for system maintenance
- Identification and signalling (visual and audible) of the presence of the
detectors and remote fire alarm activation buttons
- Possibility of delayed de-energisation of restraint solenoids
Standards compliance:EN54-2 (control unit) and EN54-4 (power supply unit)