Art. 52002 - Single-zone fire alarm control panel
Accessories for the installation of fire protection systems according to EN54.
PRODUCT CODE:
52002
EMPLOYMENT:
Fire alarm system
PACKAGE:
Beige ABS wall-mounted enclosure, electronic board
VARIANTS:
CHARACTERISTICS:
Beige ABS wall-mounted enclosure equipped with panel with LEDs for indications, push-buttons and key switch [52002].
SPECIFICATIONS:
| Body dimensions | 240 x 150 x 48 mm |
| Power supply: | - Main: from mains 250 Vac 50-60 Hz - Auxiliary: supplied by No. 2 batteries 12 Vdc 1.1 / 1.3 Ah (Art. 00112 mandatory and supplied separately) |
| Operating area: | Single |
| Main panel with LEDs for illuminated indications of the operating status of the control unit, with the following displays: | - Fire alarm - Mains voltage presence / absence - Presence / absence of auxiliary voltage (battery) - Central unit general fault - Detector(s) line failure - Line failure of remote alarm activation button(s) - Manual out-of-service status of the control unit - Siren line failure - Feeding electromagnets - System failure |
| Buttons: | - Manual override of siren line and push-button and detector lines - Recovery from alarm, fault or out-of-service condition |
| Key switch: | For access to the central unit's Level 2 functions |
| Inputs (on terminal board): | - Heat and smoke detector line(s) (up to 8 units, mandatory and supplied separately, certified EN54-5 - heat Art. 05204A and EN54-7 - smoke Art. 05203A) - Remote alarm activation button(s) line (up to 5 units, min. 2 mandatory supplied separately, EN54-11 certified Art. 05110R) - Line remote button(s) manual release electromagnets - External buzzer alarm silencing/reactivation button after alarm (Art. No. 05115) |
| Outputs (on terminal board): | - Electromagnets line (up to 4 - 24 Vdc - Max. 300 mA total) - Output for connection to up to 2 external sirens (additional mandatory electronic siren supplied separately and EN54-3 certified, Art. 05207) operating in parallel with the internal ringer of the control unit - N°1 relay output on COM. / N.O. / N.C. contacts (2 A) for signalling external out-of-service / central unit failure |
| Other expected functions: | - Mains presence / power failure signalling - Auxiliary presence/voltage failure signalling (batteries) - Checking the quality status of batteries - Muting the alarm signal of the control unit - Reactivation of alarm signalling following a new alert alarm by any of the detection devices - Possibility to put the control unit out of service manually for system maintenance - Identification and signalling (visual and audible) of the presence of the detectors and remote fire alarm activation buttons - Possibility of delayed de-energisation of restraint solenoids |
| Standards compliance: | EN54-2 (control unit) and EN54-4 (power supply unit) |