Skip links

Need more information?

Do not hesitate to contact us via form or chat

Contact

Art. 55003 - Electromagnet with 'Exit System' management electronics to apply

Maxi series electromagnet with electronic board for the management and control of opening of emergency exits equipped with Safety series electromagnets, with Hall effect electromagnet status sensor, optical signalling of locked/unlocked electromagnet status by means of red - green Jumboled, buzzer for acoustic signalling of Alarm status, internal relay on locked/unlocked electromagnet status with C. - N.O. - N.C. contacts and rechargeable buffer battery.

PRODUCT CODE:
55003
EMPLOYMENT:
Maxi series electromagnets with electronic board for the management and opening control of emergency exits equipped with Safety series electromagnets
PACKAGE:
Electromagnet with housing and fixing bracket, counterplate and buffer battery. On request: magnetic sensor Art. 02221 - 02223
VARIANTS:

CHARACTERISTICS:

Silver anodised aluminium Maxi series solenoid, with satin-finish stainless steel casing, nickel-plated steel fixing bracket. Retaining plate with anti-magnetism residual pin (to be fixed on the sash) [55003].

SPECIFICATIONS:

Carter Dimensions280 x 158 x 115 mm
Counterplate dimensions185 x 60 x 16 mm
Tensile force600 kg
Card power supply12 Vac / dc
Rechargeable buffer battery12 Vdc / 2.2 Ah
Adjustable timer for alarm-only or delayed opening request5 - 60 sec
Adjustable timer for delayed opening alarm from outside (can be enabled)10 - 120 sec
Adjustable timer for manual opening by push-button or console with reclosing at door approach0 - 5 sec
Adjustable timer for manual opening by push-button or console with reclosing if the door is not opened0 - 60 sec
Adjustable timer for prolonged door opening alarm (can be enabled)10 - 120 sec
Inputs with N.O. contact for:- Immediate opening
- External key switch opening with delayed alarm
- Delayed opening or opening request with alarm
- Emergency
- Block
- Resetting Alarms
Outputs with N.O. relay contact for:- Electromagnet status unlocked / locked (double switch)
- Opening or delayed opening request alarm
- Prolonged door opening alarm
- Emergency opening alarm
- Delayed alarm for opening from outside
- Fault Alarm
- Activating the system
- Open / closed sash position (Open Collector)